Monthly functional and annual 90-minute discharge testing for emergency lighting units and illuminated exit signs, documented per unit.
Fortress Fire Protection — Boyd, TX 76023 · Phone: +1-817-527-9900 · Email: info@fortressfireprotection.org · Texas firm registrations: ECR-3530956 · ACR-3532428
No. The SFMO does not issue a separate registration for emergency lighting. Testing obligations come from the fire code your city or county has adopted, built on NFPA 101, and are enforced by the local fire marshal rather than the state.
A 30-second functional test every 30 days, plus a full 90-minute annual discharge test confirming the batteries can carry the required load for the whole duration, per NFPA 101.
An initial average of about 1 footcandle along the path of egress, staying above roughly 0.6 footcandle by the end of the 90-minute duration test.
Any exit sign with a battery-powered emergency light source follows the same monthly and annual test cycle as the rest of the emergency lighting system.